Server Rooms & Subfloors

Combustion in a server room may occur from a variety of sources, including a faulty hard drive, an electrical short or malfunctioning overhead lights. In the subfloors below, electrical malfunction from a cable or wire can cause a fire in the space and subsequently into the server room above.

VESDA

Due to high air flow and spacious environments in server rooms, Fike recommends VESDA air sampling to quickly identify smoke particles resulting from combustion. For smaller server rooms, basic spot detection may be used.

Chemical Agents

Fike usually recommends chemical agents due to their ability to reach full concentration in just 10 seconds. However, inert gas and water mist are also viable suppression methods based on the user’s preferences such as environmental impact, cost, design flexibility and more.

Repeat

The chosen method of protection in the server room (often VESDA air sampling and chemical agent suppression) will usually be repeated in the subfloor. However, NFPA 750 9.1.1.5 states if a suppression system is provided only under a raised floor, “the gaseous system shall be either carbon dioxide or an inert gas.”

VESDA VEU 3MTankLabel_zoom_270px (1) Inert Gas Duraquench watermist Server Room Subfloor (1)

Control Rooms

Common hazards in control rooms are the result of electrical fires caused by computer hardware and controls.

Spot Detection

Because control rooms are typically smaller in scale than other areas of the data center, spot detection is standard in these applications. However, for extra reliability, VESDA air sampling may also be used.

Suppression Strategies

Viable suppression strategies for control rooms include chemical agents, inert gas and water mist.

Small Space Suppression

If an electrical cabinet is present, Fike’s Small Space Suppression provides both detection and suppression at the source of small electrical fires. A heat-reactive tubing is routed through the electrical cabinet; if an electrical fire occurs, it will melt a hole in the tubing through which chemical agent will dispense directly onto the fire.

Data Centers Fire Protection Electrical Cabinet

Uninterrupted Power Supply Rooms

UPS rooms possess several potential fire hazards, including faulty wiring which may produce electrical arcs or a malfunctioning battery which may offgas explosive hydrogen into the room.

VESDA

VESDA air sampling is recommended to quickly detect smoke particles, and gas detection is recommended to identify hydrogen and other potentially explosive gasses. These detection methods may be installed separately, or a VESDA Sensepoint XCL may be used to perform both functions.

Inert Gas

In power supply applications greater than 480V, inert gas is ideal because the agent doesn’t burn off when it breaks down. Otherwise, chemical agents may also be used.

Sensepoint XCD Inert Gas Uninterrupted Power Supply

Diesel Engines

Fuel leaks are common in diesel engines and can quickly ignite if reached by an ignition source.

Flame Detectors

Fike Flame Detectors can instantly identify the incipient stages of combustion. Combined with Fike Analytics, these devices also have the ability to detect oil leaks before combustion occurs. Otherwise, basic spot detection may be used

Water-Based System

Because diesel engines have the ability to produce large fires, water mist (Fike DuraQuench®) is ideal for these applications and uses FM-approved data center nozzles. One DuraQuench® pump skid may be zoned to protect multiple applications.

What does NFPA 75 say about ...

Gaseous Agents

The use of gaseous agents provides the potential for automatic fire suppression in the incipient fire stage so that the information technology system can continue to perform its mission with little or no interruption. Where coupled with a well-designed early warning detection system, the gas can be automatically released in the early stages of a fire scenario and, being three dimensional, it will penetrate all portions of the space protected, including internal volumes of key components of the system when they are ventilated from the room. Thus an operator does not have to be present or, if present, does not have to determine if and where the fire is occurring and how to deal with it. Gaseous agents fall into the following general categories: inert gasses and chemical agents. (D.1)

Concentration Levels

Total flooding agents are effective when the gas envelopes the protected equipment at the proper concentration, a minimum concentration is held until the ignition source is removed, and any smoldering fire that remains after flame extinguishment is controlled. This statement generally means that the enclosure to be flooded needs to be enclosed as much as possible to retain the gas discharged. Integrity of the space protected can need verification and means taken to close off openings to ensure an adequate gas concentration holding time. (D.2)

If major concerns over potential fire loss of specific critical data or equipment or serious interruption to operations cannot be resolved or alleviated by equipment redundancy, subdivision of the ITE area, or use of leased facilities, automatic gaseous agent total flooding might be the only feasible approach to handling an incipient fire situation with an acceptable minimum amount of damage. At the same time, this sophisticated protection approach requires that all environmental design criteria - for example, damper closure, fan shutdown, and sealed openings - be carefully maintained to ensure that the needed concentration for extinguishment will be achieved. (A.9.4.1)

Subfloors

Where a gaseous fire extinguishing system is provided only under a raised floor, the gaseous system shall be either carbon dioxide or an inert gas. (9.1.1.5)

Where a clean agent fire extinguishing system is provided to protect the space above the raised floor, the space under the raised floor shall be simultaneously protected by the clean agent fire extinguishing system. (9.1.1.6)

The use of carbon dioxide systems for the protection of spaces beneath the raised floor is discussed in section B.5 of NFPA 12 wherein it is pointed out that the design of such systems requires compensation for leakage and provision for a soft discharge to minimize turbulence and agent loss through perforated tiles. These same concerns exist for other inert gas clean agent systems installed in accordance with NFPA 2001. Since these spaces are usually of a very limited height, this type of fire suppression system might be easier to design and install than sprinklers. (A.9.1.1.3)

Detection

Automatic detection equipment shall be installed to provide early warning of fire. (9.2.1)

Automatic detection systems shall be installed to provide early warning of fire in the following locations:

  1. At the ceiling level throughout the ITE area.
  2. Below the raised floor of the ITE area containing cables.
  3. In the exhaust/return air stream where aisle containment systems are used.
  4. In the return air stream where the above ceiling area is used as a return air plenum (9.2.2).
Smoke Detection

Where a smoke detection system is installed for the primary purpose of summoning responsible people to the presence of a small ITE fire or electrical event that produces smoke, the system should be arranged with high sensitivity and close spacing to achieve response to low-density products of combustion suspended in air with reasonable stability and tolerance of the environment. (A.9.2.2)

Where a smoke detection system is installed for the primary purpose of initiating the release of a fire suppression agent into an ITE area, the system should be arranged with low sensitivity, spacing less than listed spacing, and should include a form of logical confirmation of the presence of products of combustion to assure that a single indication does not release the agent. (A.9.2.2)